Multiples of: 1 | Minimum Order: 1
AF80-30-11-13 100-250V50/60HZ-DC Contactor
The AF80-30-11-13 is a 3 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 37 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 125 A (AC-1) or 105 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Dimensions
Product Net Width: 82 mm
Product Net Depth / Length: 116 mm
Product Net Height: 125.5 mm
Product Net Weight: 1.21 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Number of Poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage: Auxiliary Circuit 690 V, Main Circuit 1000 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz, Control Circuit 50 / 60 Hz, Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 125 A, (690 V) 60 °C 100 A, (690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie): (415 V) 60 °C 80 A, (440 V) 60 °C 80 A, (500 V) 60 °C 65 A, (690 V) 60 °C 49 A, (1000 V) 60 °C 25 A, (380 / 400 V) 60 °C 80 A, (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-3e (Ie): (415 V) 60 °C 80 A, (440 V) 60 °C 80 A, (500 V) 60 °C 65 A, (690 V) 60 °C 49 A, (380 / 400 V) 60 °C 80 A, (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-15 (Ie): (500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 125 A, (110 V) 2 Poles in Series, 60 °C 100 A, (110 V) 2 Poles in Series, 70 °C 85 A, (110 V) 3 Poles in Series, 40 °C 125 A, (110 V) 3 Poles in Series, 60 °C 100 A, (110 V) 3 Poles in Series, 70 °C 85 A, (220 V) 3 Poles in Series, 40 °C 125 A, (220 V) 3 Poles in Series, 60 °C 100 A, (220 V) 3 Poles in Series, 70 °C 85 A, (72 V) 1-Pole, 40 °C 125 A, (72 V) 1-Pole, 60 °C 100 A, (72 V) 1-Pole, 70 °C 85 A, (72 V) 2 Poles in Series, 40 °C 125 A, (72 V) 2 Poles in Series, 60 °C 100 A, (72 V) 2 Poles in Series, 70 °C 85 A, (72 V) 3 Poles in Series, 40 °C 125 A, (72 V) 3 Poles in Series, 60 °C 100 A, (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 125 A, (110 V) 2 Poles in Series, 60 °C 100 A, (110 V) 2 Poles in Series, 70 °C 85 A, (110 V) 3 Poles in Series, 40 °C 125 A, (110 V) 3 Poles in Series, 60 °C 100 A, (110 V) 3 Poles in Series, 70 °C 85 A, (220 V) 3 Poles in Series, 40 °C 125 A, (220 V) 3 Poles in Series, 60 °C 100 A, (220 V) 3 Poles in Series, 70 °C 85 A, (72 V) 1-Pole, 40 °C 125 A, (72 V) 1-Pole, 60 °C 100 A, (72 V) 1-Pole, 70 °C 85 A, (72 V) 2 Poles in Series, 40 °C 125 A, (72 V) 2 Poles in Series, 60 °C 100 A, (72 V) 2 Poles in Series, 70 °C 85 A, (72 V) 3 Poles in Series, 40 °C 125 A, (72 V) 3 Poles in Series, 60 °C 100 A, (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 125 A, (110 V) 2 Poles in Series, 60 °C 100 A, (110 V) 2 Poles in Series, 70 °C 85 A, (110 V) 3 Poles in Series, 40 °C 125 A, (110 V) 3 Poles in Series, 60 °C 100 A, (110 V) 3 Poles in Series, 70 °C 85 A, (220 V) 3 Poles in Series, 40 °C 125 A, (220 V) 3 Poles in Series, 60 °C 100 A, (220 V) 3 Poles in Series, 70 °C 85 A, (72 V) 1-Pole, 40 °C 125 A, (72 V) 1-Pole, 60 °C 100 A, (72 V) 1-Pole, 70 °C 85 A, (72 V) 2 Poles in Series, 40 °C 125 A, (72 V) 2 Poles in Series, 60 °C 100 A, (72 V) 2 Poles in Series, 70 °C 85 A, (72 V) 3 Poles in Series, 40 °C 125 A, (72 V) 3 Poles in Series, 60 °C 100 A, (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-13 (Ie): (24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.27 A / 60 W, (250 V) 0.27 A / 68 W, (400 V) 0.15 A / 60 W, (500 V) 0.13 A / 65 W, (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe): (400 V) 37 kW, (415 V) 45 kW, (440 V) 45 kW, (500 V) 45 kW, (690 V) 45 kW, (1000 V) 35 kW, (380 / 400 V) 37 kW, (220 / 230 / 240 V) 22 kW
Rated Operational Power AC-3e (Pe): (415 V) 45 kW, (440 V) 45 kW, (500 V) 45 kW, (690 V) 45 kW, (380 / 400 V) 37 kW, (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
for 0.1 s 140 A, for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 1000 V, acc. to IEC 60947-5-1 690 V, acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Maximum Electrical Switching Frequency: (AC-1) 600 cycles per hour, (AC-15) 1200 cycles per hour, (AC-2 / AC-4) 150 cycles per hour, (AC-3) 1200 cycles per hour, (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V, 60 Hz 100 ... 250 V
DC Operation: 100 ... 250 V
Coil Consumption: Average Holding Value 50 / 60 Hz 4 V·A, Average Holding Value 50 Hz 4 V·A, Average Holding Value 60 Hz 4 V·A, Average Holding Value DC 2 W, Average Holding Value, from Warm State 2 W
Power Loss: at 6 A per Pole 0.1 W, at Rated Operating Conditions AC-1 per Pole 7.6 W, at Rated Operating Conditions AC-3 per Pole 3 W
Operate Time: Between Coil De-energization and NC Contact Closing 19 ... 105 ms, Between Coil De-energization and NO Contact Opening 17 ... 100 ms, Between Coil Energization and NC Contact Opening 38 ... 95 ms, Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied): 2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 6 ... 50 mm², Flexible with Insulated Ferrule 1/2x 6 ... 50 mm², Rigid Stranded 1x 6 ... 70 mm², Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm, Control Circuit 10 mm, Main Circuit 17 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver: Pozidriv PZ
Tightening Torque: Auxiliary Circuit 1.2 N·m, Control Circuit 1.2 N·m, Main Circuit 6 N·m
Terminal Type: Screw Terminals
Product Name: Block Contactor
Technical UL/CSA
NEMA Size: 3
Continuous Current Rating NEMA: 90 A
Horsepower Rating NEMA: (200 V AC) Three Phase 25 Hp, (230 V AC) Three Phase 30 Hp, (460 V AC) Three Phase 50 Hp, (575 V AC) Three Phase 50 Hp
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 105 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 7-1/2 hp, (200 ... 208 V AC) Three Phase 25 hp, (220 ... 240 V AC) Three Phase 30 hp, (240 V AC) Single Phase 15 hp, (440 ... 480 V AC) Three Phase 60 hp, (550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA: Rigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb, Control Circuit 11 in·lb, Main Circuit 53 in·lb
Full Load Amps Motor Use: (120 V AC) Single Phase 80 A, (200 ... 208 V AC) Three Phase 78.2 A, (220 ... 240 V AC) Three Phase 80 A, (240 V AC) Single Phase 68 A, (440 ... 480 V AC) Three Phase 77 A
(550 ... 600 V AC) Three Phase 77 A
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C, Close to Contactor without Thermal O/L Relay -40 ... 70 °C, Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand: Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible: Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Closed, Shock Direction: A 25 g, Closed, Shock Direction: B1 25 g, Closed, Shock Direction: B2 15 g, Closed, Shock Direction: C1 25 g, Closed, Shock Direction: C2 25 g, Open, Shock Direction: B1 5 g
Resistance to Vibrations: 3g Closed Position & 3g Open Position 5 ... 300 Hz
Pollution Degree: 3
Brand |
ABB |
|
£400.83
per 1 (ex. VAT)£481.00
per 1 (inc. VAT)
AF80-30-11-13 100-250V50/60HZ-DC Contactor
The AF80-30-11-13 is a 3 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 37 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 125 A (AC-1) or 105 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Dimensions
Product Net Width: 82 mm
Product Net Depth / Length: 116 mm
Product Net Height: 125.5 mm
Product Net Weight: 1.21 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Number of Poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage: Auxiliary Circuit 690 V, Main Circuit 1000 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz, Control Circuit 50 / 60 Hz, Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 125 A, (690 V) 60 °C 100 A, (690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie): (415 V) 60 °C 80 A, (440 V) 60 °C 80 A, (500 V) 60 °C 65 A, (690 V) 60 °C 49 A, (1000 V) 60 °C 25 A, (380 / 400 V) 60 °C 80 A, (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-3e (Ie): (415 V) 60 °C 80 A, (440 V) 60 °C 80 A, (500 V) 60 °C 65 A, (690 V) 60 °C 49 A, (380 / 400 V) 60 °C 80 A, (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-15 (Ie): (500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 125 A, (110 V) 2 Poles in Series, 60 °C 100 A, (110 V) 2 Poles in Series, 70 °C 85 A, (110 V) 3 Poles in Series, 40 °C 125 A, (110 V) 3 Poles in Series, 60 °C 100 A, (110 V) 3 Poles in Series, 70 °C 85 A, (220 V) 3 Poles in Series, 40 °C 125 A, (220 V) 3 Poles in Series, 60 °C 100 A, (220 V) 3 Poles in Series, 70 °C 85 A, (72 V) 1-Pole, 40 °C 125 A, (72 V) 1-Pole, 60 °C 100 A, (72 V) 1-Pole, 70 °C 85 A, (72 V) 2 Poles in Series, 40 °C 125 A, (72 V) 2 Poles in Series, 60 °C 100 A, (72 V) 2 Poles in Series, 70 °C 85 A, (72 V) 3 Poles in Series, 40 °C 125 A, (72 V) 3 Poles in Series, 60 °C 100 A, (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 125 A, (110 V) 2 Poles in Series, 60 °C 100 A, (110 V) 2 Poles in Series, 70 °C 85 A, (110 V) 3 Poles in Series, 40 °C 125 A, (110 V) 3 Poles in Series, 60 °C 100 A, (110 V) 3 Poles in Series, 70 °C 85 A, (220 V) 3 Poles in Series, 40 °C 125 A, (220 V) 3 Poles in Series, 60 °C 100 A, (220 V) 3 Poles in Series, 70 °C 85 A, (72 V) 1-Pole, 40 °C 125 A, (72 V) 1-Pole, 60 °C 100 A, (72 V) 1-Pole, 70 °C 85 A, (72 V) 2 Poles in Series, 40 °C 125 A, (72 V) 2 Poles in Series, 60 °C 100 A, (72 V) 2 Poles in Series, 70 °C 85 A, (72 V) 3 Poles in Series, 40 °C 125 A, (72 V) 3 Poles in Series, 60 °C 100 A, (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 125 A, (110 V) 2 Poles in Series, 60 °C 100 A, (110 V) 2 Poles in Series, 70 °C 85 A, (110 V) 3 Poles in Series, 40 °C 125 A, (110 V) 3 Poles in Series, 60 °C 100 A, (110 V) 3 Poles in Series, 70 °C 85 A, (220 V) 3 Poles in Series, 40 °C 125 A, (220 V) 3 Poles in Series, 60 °C 100 A, (220 V) 3 Poles in Series, 70 °C 85 A, (72 V) 1-Pole, 40 °C 125 A, (72 V) 1-Pole, 60 °C 100 A, (72 V) 1-Pole, 70 °C 85 A, (72 V) 2 Poles in Series, 40 °C 125 A, (72 V) 2 Poles in Series, 60 °C 100 A, (72 V) 2 Poles in Series, 70 °C 85 A, (72 V) 3 Poles in Series, 40 °C 125 A, (72 V) 3 Poles in Series, 60 °C 100 A, (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-13 (Ie): (24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.27 A / 60 W, (250 V) 0.27 A / 68 W, (400 V) 0.15 A / 60 W, (500 V) 0.13 A / 65 W, (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe): (400 V) 37 kW, (415 V) 45 kW, (440 V) 45 kW, (500 V) 45 kW, (690 V) 45 kW, (1000 V) 35 kW, (380 / 400 V) 37 kW, (220 / 230 / 240 V) 22 kW
Rated Operational Power AC-3e (Pe): (415 V) 45 kW, (440 V) 45 kW, (500 V) 45 kW, (690 V) 45 kW, (380 / 400 V) 37 kW, (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
for 0.1 s 140 A, for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 1000 V, acc. to IEC 60947-5-1 690 V, acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Maximum Electrical Switching Frequency: (AC-1) 600 cycles per hour, (AC-15) 1200 cycles per hour, (AC-2 / AC-4) 150 cycles per hour, (AC-3) 1200 cycles per hour, (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V, 60 Hz 100 ... 250 V
DC Operation: 100 ... 250 V
Coil Consumption: Average Holding Value 50 / 60 Hz 4 V·A, Average Holding Value 50 Hz 4 V·A, Average Holding Value 60 Hz 4 V·A, Average Holding Value DC 2 W, Average Holding Value, from Warm State 2 W
Power Loss: at 6 A per Pole 0.1 W, at Rated Operating Conditions AC-1 per Pole 7.6 W, at Rated Operating Conditions AC-3 per Pole 3 W
Operate Time: Between Coil De-energization and NC Contact Closing 19 ... 105 ms, Between Coil De-energization and NO Contact Opening 17 ... 100 ms, Between Coil Energization and NC Contact Opening 38 ... 95 ms, Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied): 2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 6 ... 50 mm², Flexible with Insulated Ferrule 1/2x 6 ... 50 mm², Rigid Stranded 1x 6 ... 70 mm², Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm, Control Circuit 10 mm, Main Circuit 17 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver: Pozidriv PZ
Tightening Torque: Auxiliary Circuit 1.2 N·m, Control Circuit 1.2 N·m, Main Circuit 6 N·m
Terminal Type: Screw Terminals
Product Name: Block Contactor
Technical UL/CSA
NEMA Size: 3
Continuous Current Rating NEMA: 90 A
Horsepower Rating NEMA: (200 V AC) Three Phase 25 Hp, (230 V AC) Three Phase 30 Hp, (460 V AC) Three Phase 50 Hp, (575 V AC) Three Phase 50 Hp
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 105 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 7-1/2 hp, (200 ... 208 V AC) Three Phase 25 hp, (220 ... 240 V AC) Three Phase 30 hp, (240 V AC) Single Phase 15 hp, (440 ... 480 V AC) Three Phase 60 hp, (550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA: Rigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb, Control Circuit 11 in·lb, Main Circuit 53 in·lb
Full Load Amps Motor Use: (120 V AC) Single Phase 80 A, (200 ... 208 V AC) Three Phase 78.2 A, (220 ... 240 V AC) Three Phase 80 A, (240 V AC) Single Phase 68 A, (440 ... 480 V AC) Three Phase 77 A
(550 ... 600 V AC) Three Phase 77 A
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C, Close to Contactor without Thermal O/L Relay -40 ... 70 °C, Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand: Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible: Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Closed, Shock Direction: A 25 g, Closed, Shock Direction: B1 25 g, Closed, Shock Direction: B2 15 g, Closed, Shock Direction: C1 25 g, Closed, Shock Direction: C2 25 g, Open, Shock Direction: B1 5 g
Resistance to Vibrations: 3g Closed Position & 3g Open Position 5 ... 300 Hz
Pollution Degree: 3