My Part Number:
Part Number: KFU8-SR-EX1.W
Manufacturer Code: 204137
Multiples of: 1 | Minimum Order: 1
Switch Amplifier KFU8-SR-Ex1.W
• 1-channel isolated barrier
• Universal usage at different power supplies
• Dry contact or NAMUR inputs
• Relay contact output
• Line fault detection (LFD)
• Reversible mode of operation
• Up to SIL 2 (SC 3) acc. to IEC/EN 61508
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.
The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The barrier output changes state when the input signal changes state. The normal output state can be reversed using switch S1. Switch S3 is used to enable or disable line fault detection of the field circuit.
During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.
Brand |
PEPPERL & FUCHS |
|
£174.17
per 1 (ex. VAT)£209.00
per 1 (inc. VAT)
Switch Amplifier KFU8-SR-Ex1.W
• 1-channel isolated barrier
• Universal usage at different power supplies
• Dry contact or NAMUR inputs
• Relay contact output
• Line fault detection (LFD)
• Reversible mode of operation
• Up to SIL 2 (SC 3) acc. to IEC/EN 61508
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.
The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The barrier output changes state when the input signal changes state. The normal output state can be reversed using switch S1. Switch S3 is used to enable or disable line fault detection of the field circuit.
During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.
Brand |
PEPPERL & FUCHS |
|