Fieldbus Coupler PROFINET IO - 3rd Generation, Advanced
This fieldbus coupler connects the WAGO I/O System 750 to PROFINET IO (open, real-time Industrial ETHERNET automation standard). The coupler identifies the connected I/O modules and creates local process images for maximum two I/O controllers and one I/O supervisor according to preset configurations. This process image may include a mixed arrangement of analog (word-by-word data transfer) or complex modules and digital (bit-by-bit data transfer) modules.
The fieldbus coupler operates as an I/O device in the network. It features an integrated 2-port switch, simplifying the creation of a line structure without additional network components. The device name can be assigned via DCP protocol or a default name can be instantiated via DIP switch.
Communication: PROFINET IO
Device-specific: Supported profiles: PROFIsafe V2, PROFIenergy V1.0; ID code: Vendor ID: 0x011D; Device ID: 0x02EE; Module ID: 0x01000177 (firmware version 01, 02), 0x02000177 (from firmware version 03)
Baud rate: 10/100 Mbit/s (10 Mbit/s (ETHERNET protocols), 100 Mbit/s full duplex (PROFINET IO))
Bus segment length (max.): 100 m
Transmission medium: Twisted Pair S-UTP; 100 Ω; Cat. 5
Number of modules per node (max.): 250
Number of modules without a bus extension (max.): 64
Input and output process image (fieldbus) max.: 512 bytes/512 bytes
Supply voltage (system): 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Current consumption (5 V system supply): 450mA
Total current (system supply): 1,700mA
Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts
Input current (typ.): 500mA
Power supply efficiency (typ.) at nominal load (24 V): 90%
Isolation: 500 V system/field
Number of outgoing power jumper contacts: 3
Current carrying capacity (power jumper contacts): 10A
Brand |
WAGO |
|
£420.79
per 1 (ex. VAT)£504.95
per 1 (inc. VAT)
Fieldbus Coupler PROFINET IO - 3rd Generation, Advanced
This fieldbus coupler connects the WAGO I/O System 750 to PROFINET IO (open, real-time Industrial ETHERNET automation standard). The coupler identifies the connected I/O modules and creates local process images for maximum two I/O controllers and one I/O supervisor according to preset configurations. This process image may include a mixed arrangement of analog (word-by-word data transfer) or complex modules and digital (bit-by-bit data transfer) modules.
The fieldbus coupler operates as an I/O device in the network. It features an integrated 2-port switch, simplifying the creation of a line structure without additional network components. The device name can be assigned via DCP protocol or a default name can be instantiated via DIP switch.
Communication: PROFINET IO
Device-specific: Supported profiles: PROFIsafe V2, PROFIenergy V1.0; ID code: Vendor ID: 0x011D; Device ID: 0x02EE; Module ID: 0x01000177 (firmware version 01, 02), 0x02000177 (from firmware version 03)
Baud rate: 10/100 Mbit/s (10 Mbit/s (ETHERNET protocols), 100 Mbit/s full duplex (PROFINET IO))
Bus segment length (max.): 100 m
Transmission medium: Twisted Pair S-UTP; 100 Ω; Cat. 5
Number of modules per node (max.): 250
Number of modules without a bus extension (max.): 64
Input and output process image (fieldbus) max.: 512 bytes/512 bytes
Supply voltage (system): 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Current consumption (5 V system supply): 450mA
Total current (system supply): 1,700mA
Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts
Input current (typ.): 500mA
Power supply efficiency (typ.) at nominal load (24 V): 90%
Isolation: 500 V system/field
Number of outgoing power jumper contacts: 3
Current carrying capacity (power jumper contacts): 10A