My Part Number:
Part Number: 750-625/000-001
Manufacturer Code: 750-625/000-001
Multiples of: 1 | Minimum Order: 1
Power Supply - 24 VDC, Intrinsically safe
This supply module powers all intrinsically safe 750 Series Ex i Modules. It also monitors the power supply to the downstream Ex i segment and separates the intrinsically safe from the non-intrinsically safe section of the WAGO I/O System 750. The input and output sides are electrically isolated from each other.
The maximum current provided by the supply module is 1.0 A. When configuring the Ex i segment, the total current must not be exceeded.
In the event of a short circuit or overload, electronic monitoring automatically switches off the output voltage. After eliminating the fault, the output voltage is reactivated within approximately ten seconds.
If, due to load conditions, more than one supply module is required per station, four distance modules (750‐616) must be placed between the intrinsically safe sections.
Indicators:
• Green LED (input voltage)
• Green/red LED (output voltage available/not available)
Input voltage (note): 24 VDC (−25 % … +30 %)
Fuse: electronic
Power consumption Pmax.: 29 W
Safety: yes
Supply voltage (system): 5 VDC; via data contacts
Current consumption (5 V system supply): 7.5mA
Supply voltage (field): 24 VDC (-25 … +30 %); (Adjacent Ex i modules are supplied with UO = max. 27.3 V); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission via spring contact)
Supply voltage: 24 VDC; (-25 % … +30 %); Input voltage
Power loss Pl: < 5 W
Indicators: LED (A) green: Status voltage supply: Input; LED (B) green/red: Status voltage supply: Output
Number of outgoing power jumper contacts: 2
Current carrying capacity (power jumper contacts): 1A
Marking: ATEX/IECEx: II 3G Ex ec IIC T4 Gc
Brand |
WAGO |
|
£443.20
per 1 (ex. VAT)£531.84
per 1 (inc. VAT)
Power Supply - 24 VDC, Intrinsically safe
This supply module powers all intrinsically safe 750 Series Ex i Modules. It also monitors the power supply to the downstream Ex i segment and separates the intrinsically safe from the non-intrinsically safe section of the WAGO I/O System 750. The input and output sides are electrically isolated from each other.
The maximum current provided by the supply module is 1.0 A. When configuring the Ex i segment, the total current must not be exceeded.
In the event of a short circuit or overload, electronic monitoring automatically switches off the output voltage. After eliminating the fault, the output voltage is reactivated within approximately ten seconds.
If, due to load conditions, more than one supply module is required per station, four distance modules (750‐616) must be placed between the intrinsically safe sections.
Indicators:
• Green LED (input voltage)
• Green/red LED (output voltage available/not available)
Input voltage (note): 24 VDC (−25 % … +30 %)
Fuse: electronic
Power consumption Pmax.: 29 W
Safety: yes
Supply voltage (system): 5 VDC; via data contacts
Current consumption (5 V system supply): 7.5mA
Supply voltage (field): 24 VDC (-25 … +30 %); (Adjacent Ex i modules are supplied with UO = max. 27.3 V); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission via spring contact)
Supply voltage: 24 VDC; (-25 % … +30 %); Input voltage
Power loss Pl: < 5 W
Indicators: LED (A) green: Status voltage supply: Input; LED (B) green/red: Status voltage supply: Output
Number of outgoing power jumper contacts: 2
Current carrying capacity (power jumper contacts): 1A
Marking: ATEX/IECEx: II 3G Ex ec IIC T4 Gc
Brand |